RFQ itemInformation to provideProcurement reason
01
VCB model, installation type and quantity
Complete model and suffix; withdrawable, side-mounted, three-position GIS or outdoor type; panel or site position; quantity; new or replacement scope.
Lets procurement compare the same product configuration and included supply across quotations.
02
Rated voltage, frequency, current and insulation
Rated kV, Hz and A; power-frequency and lightning-impulse withstand levels; system earthing and project insulation requirements.
Ensures the selected VCB matches the network voltage, continuous load and insulation coordination.
03
Short-circuit and operating duty
Breaking and making current, short-time and peak withstand current, duration, operating sequence and any capacitor, motor or frequent-switching duty.
Confirms that the breaker is rated for the calculated fault level and intended switching service.
04
Primary interface and dimensions
Phase spacing, contacts or terminals, mounting centres, handcart or chassis, cabinet width and depth, clearances, earthing and drawing revision.
Confirms mechanical fit and a reliable primary connection to the panel or outdoor structure.
05
Mechanism, control and interlocks
Charging supply, closing and tripping coils, control voltage, secondary plug and pinout, auxiliary contacts, interlocks, indication and sequence.
Prevents control-wiring, operating-sequence and safety-interlock mismatches during installation.
06
Service conditions, standards and documents
Indoor or outdoor service; altitude, temperature, pollution, wind or seismic duty; required standard and edition; drawings, inspection and submission schedule.
Defines environmental performance, compliance evidence and documentation before purchase-order release.